‎Chapter 4 PAS Application Software

General Meter Setup

64

Series PM175 Powermeters

Basic Meter Setup

Before operating your meter, provide the device with basic
information about your electrical network.

To enter the Setup dialog, select the device site from the list
box on the PAS toolbar, and then select General Setup from
the Meter Setup menu.

The following table lists available device configuration options.

Parameter

Options

Default

Description

Basic Configuration

Wiring mode

See Table below

4LN3

The wiring connection of the device

PT ratio

1

1.0-6500.0

1.0

The phase potential transformer’s
primary to secondary ratio

PT Ratio multiplier

Ч1, Ч10

Ч1

PT Ratio multiplication factor. Used in
extra high voltage networks to

accommodate the PT ratio for 500 kV
and higher networks.

CT primary current 1-20,000 A

5 A

The primary rating of the phase

current transformer

Nominal voltage

10-690 V

120 V

The nominal secondary line-to-neutral
(in 4LN3, 3LN3 and 3BLN3 wiring
modes) or line-to-line (in 4LL3, 3LL3,

3BLL3, 3OP2, 3OP3 and 3DIR modes)
voltage. Used as a reference voltage

for the EN50160 evaluation.

Maximum demand
load current

0-20,000 A

0

The maximum demand load current
(0 = CT primary)

Nominal frequency 50,60 Hz

60 Hz

The nominal line frequency