SATEC PM175 Manual User Manual

Page 92

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Recorders

92

Series PM175 Powermeters

3. Select the maximum number of records you want to be

recorded in the file.

The number of records in the waveform log file needed to

store one waveform event (series) is defined as follows:

Number of Records per Series = Sampling Rate (Samples
per Cycle) x Number of Cycles per Event / 512

The total number of records you must allocate to store the
required number of events (series) is defined as follows:

Number of Records = Number of Records per Series x

Number of Series

For example, if you want to record a 64-cycle waveform
sampled at a rate of 32 samples per cycle, the number of
records required for one waveform series would be:

Number of Records per Series = (32 x 64)/512 = 4.

If you want to allocate space sufficient to store 20
waveform events (series), you should set up the
waveform log file for 4 x 20 = 80 records.

4. Click OK, and send your setup to the meter or save to the

database.

5. Click “Setup Recorder”, or click on the “Waveform

Recorder” tab.

The following table lists available waveform options.

Option

Format/Range

Description

Samples per Cycle

32, 64, 128

Waveform sampling rate

Cycles per Series

16-2560 (32 samples/cycle),
8-1280 (64 samples/cycle),

4-640 (128 samples/cycle)

Defines the total duration of the
waveform per event/series

Before Cycles

1-20

Defines the number of cycles to be
recorded prior to event

Num. of Channels

1-6

The number of the simultaneously
recorded channels

6. Select the sampling rate for waveforms.