SATEC PM175 Manual User Manual

Page 87

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Recorders

Series PM175 Powermeters

87

Option

Range

Description

Size

The memory size allocated to the file. Set automatically depending
on the size of the records and the number of records in the file.

Sections/Channels 0-14

The numbers of sections in a multi-section TOU profile data log
file, or the number of recording channels in a waveform log file

Num. of Records 0-65535

Allocates the file memory for predefined number of records

Record size

The size of the file record for a single channel or a section. Set
automatically depending on the file and on the number of

parameters in the data record

Parameters

0-16

The number of parameters in a single data record (not including
the EN50160 statistics files)

Memory is allocated for each file statically when you set up
your files and will not change unless you re-organize the files.
The meter automatically performs de-fragmentation of the
memory each time you re-organize your files. This helps keep
all free memory in one continuous block and thus prevents
possible leakage of memory caused by fragmentation.

To change the file properties or to allocate the memory for a

new file, double click on the file partition you want to change,
select desired parameters for your log, and click OK. For your
reference, the record size and the number of records available
for your file are reported in the dialog box.

To delete an existing file partition, click on Delete and then
click OK.

The following table shows how to calculate a file size for
different log files.

File

Record Size, Bytes

File Size, Bytes

Event Log

20

Record size

Number of records

Data Log

12 + 4

Number of parameters

Record size

Number of records

EN50160 Compliance
Statistics, Data log #9

148 (per channel)

12

Record size

Number of records

EN50160 Harmonics
Survey, Data log #10

220 (per channel)

3

Record size

Number of records

TOU Profile Log, Data

log #16

12 + 4

(Number of season

tariffs + 1 if the TOU summary

register is ordered)

Record size

Number of TOU registers x

Number of records (

2 if the maximum

demand profile is also ordered)

Waveform Log

1068 (per channel)

Record size

Number of Channels x

Number of series (events)

Number of

records per series

EN50160 Power Quality
Log

32

Record size

Number of records

For more information on configuring specific files, see
“Configuring Data Log Files” and “Configuring Waveform Files”
below.

The memory is pre-configured for common data trending and
fault recording applications as shown in the following table.

No.

File

Type

Size,

Bytes

Channels Number of

Records

Number of

Events

Description

1

Event log

Wrap
around

20000

1000

1000

2

Data log #1

Wrap
around

109440

1440

1440

Configured for data
trending

3

Data log #2

Wrap
around

109440

1440

1440

Configured for data
trending

10

Data log #9

Wrap

around

21312

12

12

12

Configured for

EN50160
compliance statistics