‎Chapter 3 Display Operations

Menu Operations

Series PM175 Powermeters

53

Label Parameter

Options

Description

Lo

Zero scale

Low engineering scale (in primary
units) for the analog output
corresponding to a lowest (zero)

output current (0 or 4 mA)

Hi

Full scale

High engineering scale (in primary
units) for the analog output

corresponding to a highest output
current (1 or 20 mA)

Analog expander outputs are not operational until you globally

enable the analog expander option in your meter through the

Device

Options

menu.

Timers Setup

The PM175 is provided with four interval timers. When
enabled, a timer generates periodic events in predefined
intervals that can trigger setpoints to produce periodic actions
like periodic data trending. To enter the menu, select the “t-r”
entry from the main menu and press the ENTER button.

Use the UP and DOWN arrow buttons to scroll to the desired

timer.

To change the time period for the timer:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to enter the desired

interval value in seconds. Intervals from 1 to 9999
seconds are allowed. Resetting the interval to 0 disables
the timer.

3. Press ENTER to confirm your changes and to save the

new settings, or press ESC to discard changes.

4. You are returned to the middle window to select another

timer or exit the menu.

To exit the menu, press ESC.

Display Setup

This menu allows you to configure options for the meter
display, and view display and device firmware versions. To
enter the menu, select the “diSP” entry from the main menu
and press the ENTER button.

To select a setup option:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to scroll to the

desired option.

To change the option:

1. Press the SELECT button to activate the lower window.
2. Use the UP and DOWN arrow buttons to select the

desired option.

3. Press ENTER to confirm the changes and to save your

new setting, or press ESC to discard changes.

To exit the menu, press ESC.

The following table lists available options.

t-r

0

t-r.1

diSP

1.0

UPdt