Relay outputs, Digital inputs, Optional analog inputs – SATEC PM175 Manual User Manual

Page 141: Optional analog outputs

Advertising
background image

‎Appendix A Technical Specifications

Series PM175 Powermeters

141

5A secondary

Operating range: continuous 10A RMS Burden: < 0.1 VA
Overload withstand: 15A RMS continuous, 300A RMS for 1

second

1A secondary

Operating range: continuous 2A RMS Burden: < 0.02 VA
Overload withstand: 6A RMS continuous, 80A RMS for 1
second

Relay Outputs

2 relays rated at 3A/250 VAC; 3A/30 VDC, 2 contacts (SPST
Form A)
Wire size: 14 AWG (up to 1.5 mm

2

)

Galvanic isolation:

Between contacts and coil: 2000 VAC 1 min
Between open contacts: 1000 VAC

Operate time: 10 ms max.
Release time: 5 ms max.
Update time: 1 cycle

Digital Inputs

2 Digital Inputs Dry Contacts
Wire size: 14 AWG (up to 1.5 mm

2

)

Galvanic isolation: 2000V RMS
Internal power supply 15V
Scan time: 1 ms

Optional Analog Inputs

2 Analog Inputs (optically isolated)
Ranges (upon order):

1 mA (100% overload)

0-20 mA
4-20 mA
0-1 mA (100% overload)

Wire size: 14 AWG (up to 1.5 mm

2

)

Isolation: 2,000 V RMS
Accuracy: 0.5% FS
Scan time: 1 cycle

Optional Analog Outputs

2 Analog Outputs (optically isolated)
Ranges (upon order):

1 mA, maximum load 5 k

(100% overload)

0-20 mA, maximum load 510

4-20 mA, maximum load 510

0-1 mA, maximum load 5 k

(100% overload)

Isolation: 2,000 V RMS
Power supply: internal
Accuracy: 0.5% FS
Wire size: 14 AWG (up to 1.5 mm

2

)

Update time: 1 cycle

Advertising