background image

4-4

Troubleshooting

HIM Indication

The HIM also provides visual notification of a fault.

Manually Clearing Faults

This section will contain a table that illustrates the HIM keystrokes
necessary to clear faults.

Fault Descriptions

Fault Descriptions and Configuration Parameters

Condition

Display

Drive is indicating a fault.
The LCD HIM immediately reports the fault condition by
displaying the following:
• “Faulted” appears in the status line
• Fault number
• Fault name
• Time that has passed since the fault occurred
Press Esc to regain control of the HIM

F-> Faulted

Auto

0.0

Hz

Main Menu:

Diagnostics

Parameter

— Fault — F24

DC Bus Overvolt

Time since Fault

00:23:52

Step

Key(s)

1. Press Esc to acknowledge the fault. The fault information will

be removed so that you can use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault by one of

these methods.

• Press Stop
• Cycle drive power
• Select “Clear Faults” from Diagnostic - Faults menu

Esc

No.

Name

Description

Action

1

Abs Ovespd Det

Motor speed has exceeded the limits set by parameter 30 [Rev
Speed Limit] minus parameter 335 [Abs OverSpd Lim] or parameter
31 [Fwd Speed Limit] plus parameter 335 [Abs OverSpd Lim]

1. Verify the encoder feedback is correct

polarity

2. Verify drive is not in torque mode, Par 110

[Spd/Torq ModeSel], value 2, Torque Ref
-If in torque mode, verify load is present.

3. Verify min/max settings Par 30 [Rev Speed

Lim] and Par 31 [Fwd Speed Lim].

4. Verify the load is not overhauling.

-If the load is overhauling, turn bus regulator
off, Par 414 [Brake/Bus Cnfg], bit 2 [BusRef
High].

2

Vref Decel Fail

The value of parameter 301 [Motor Spd Ref] has failed to decrease
during a ramp to zero speed stop. This could possibly be due to a
speed trim from parameters 21 [Speed Trim 1], 22 [Speed Trim 2] or
23 [Speed Trim 3].

3

Encoder 0 Loss

One of the following has occurred on encoder 0:

• missing encoder (broken wire)

• quadrature error

• phase loss

SynchLink report the event status to the VPL
which acts according to the configuration of
parameter 365 [Encdr0 Loss Cnfg]. Reconnect
encoder or replace encoder.

4

Encoder 1 Loss

One of the following has occurred on encoder10:

• missing encoder (broken wire)

• quadrature error

• phase loss

SynchLink report the event status to the VPL
which acts according to the configuration of
parameter 366 [Encdr1 Loss Cnfg].Reconnect
encoder or replace encoder.

Advertising