Appendix

A

Supplemental Information

Chapter Objectives

Specifications

For Information on …

See Page...

Specifications

A-1

DPI Communication Configurations

A-4

Output Devices

A-6

Drive, Fuse & Circuit Breaker Ratings

A-6

List of Motors with Compatible Thermistor Ratings

A-17

Spare Connectors

A-18

Dimensions

A-19

Category

Specification

Frames 1-6 (690V Drive frames 5 & 6 only)

Frames 9 & up

Protection

200-208V
Drive

240V
Drive

380/400V
Drive

480V
Drive

600V
Drive

690V
Drive

380/400V
Drive

480V
Drive

500V Drive

600V
Drive

690V
Drive

AC Input Overvoltage Trip:

247VAC

285VAC

475VAC

570VAC

690VAC

863VAC

475VAC

570V AC

611V AC

690VAC

863VAC

Bus Overvoltage Trip:

350VDC 405VDC 675VDC 810VDC 1013VDC 1164VDC 675VDC

810VDC

810VDC

1013VDC

1164VDC

Bus Undervoltage Trip:

Adjustable

Adjustable

Nominal Bus Voltage:

281VDC 324VDC 540VDC 648VDC 810VDC 931VDC 540VDC

648VDC

645VDC

810VDC

931VDC

Heat Sink Thermistor:

Monitored by microprocessor overtemp trip

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Current Limit:
Hardware Current Limit:
Instantaneous Current Limit:

Calculated value, 105% of motor rated to 200% of drive rated
105% of 3 sec. rating (158%-210%)
143% of 3 sec rating (215%-287%)

Calculated value, 105% of motor rated to 200% of drive rated
360% of rated Heavy Duty current (typical)

Line Transients:

Up to 6000 volts peak per IEEE C62.41-1991

up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity:

Showering arc transients up to 1500V peak

Showering arc transients up to 1500V peak

Power Ride-Thru:

15 milliseconds at full load

15 milliseconds at full load

Logic Control Ride-Thru

0.25 sec., drive not running

0.25 seconds, drive not running

Ground Fault Trip:

Phase-to-ground on drive output

Phase-to-ground on drive output

Short Circuit Trip:

Phase-to-phase on drive output

Phase-to-phase on drive output