1-16

Installation/Wiring

Regenerative Unit to Drive Connections

Regenerative Brake Mode

Regenerative Bus Supply Mode

Disconnecting MOVs and
Common Mode Capacitors

PowerFlex 700S drives contain protective MOVs and common mode
capacitors that are referenced to ground. To guard against drive damage,
these devices must be disconnected if the drive is installed on a resistive
grounded distribution system or an ungrounded distribution system where
the line-to-ground voltages on any phase could exceed 125% of the nominal
line-to-line voltage. To disconnect these devices, remove the jumper(s)
listed in

Table 1.F

. Jumpers can be removed by carefully pulling the jumper

straight out. See the Wiring and Grounding Guidelines for Pulse Width
Modulated (PWM) AC Drives,
publication DRIVES-IN001 for more
information on ungrounded system installation.

Table 1.F Jumper Removal

Frame(s)

Terminals
1336 Regen

PowerFlex 700S

1 - 4

DC+ & DC-

BR1 & DC-

5 & 6

DC+ & DC-

DC+ & DC-

Frame(s)

Terminals
1336 Regen

PowerFlex 700S

1 - 4

DC+ & DC-

DC+ & DC-

5 & 6

DC+ & DC-

DC+ & DC- of the Common Bus Drives

!

ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before removing/
installing jumpers. Measure the DC bus voltage at the +DC & –
DC terminals of the Power Terminal Block. The voltage must be
zero.

Frames Jumper

Component Jumper Location

No.

1

PEA

Common
Mode
Capacitors

Remove the Control Assembly and Cassette.
Jumpers are located on the drive Power Board (see

Figure 1.6

).

PEB

MOV’s

2-4

PEA

Common
Mode
Capacitors

Jumpers are located above the Power Terminal Block
(see

Figure 1.6

).

PEB

MOV’s

5

Wire

Common
Mode
Capacitors

Remove the I/O Cassette. The green/yellow jumper is
located on the back of chassis in the area shown (see

Figure 1.6

). Disconnect, insulate and secure the wire

to guard against unintentional contact with chassis or
components.

MOV’s

Note location of green/yellow jumper wire in

Figure

1.6

. Disconnect, insulate and secure the wire guard

against unintentional contact with chassis or
components.