Ac input protection devices – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 172

Advertising
background image

A-8

Supplemental Information

AC Input Protection Devices

The following tables provide informaiton

on the recommended fuses and circuit

breakers for PowerFlex 700S Phase I AC drives.

208 Volt AC Input Frames 1…6 Drive Protection Devices

Drive

Catalog

Number

Fr

am

e

kW Rating

Input

Ratings

Dual Element

Time Delay Fuse

Non-Time Delay

Fuse

Circuit

Breaker

(3)

Motor

Circuit

Protector

(5)

140M Motor Starter with Adjustable Current Range

(6)(7)

ND

HD

Amps

kVA

Min.

(1)

Max.

(2)

Min.

(1)

Max.

(2)

Max.

(4)

Max.

(5)

Available Catalog Numbers

(8)

Minimum Enclosure
Volume (in.

3

)

(9)

20DB4P2

1

0.75

0.55

3.7

1.3

6

10

6

17.5

15

7

M-C2E-B63

M-D8E-B63

7269

20DB6P8

1

1.5

1.1

6.8

2.4

10

15

10

30

30

15

M-C2E-C10

M-D8E-C10

M-F8E-C10

7269

20DB9P6

1

2.2

1.5

9.5

3.4

12

20

12

40

40

15

M-C2E-C16

M-D8E-C16

M-F8E-C16

7269

20DB015

1

4.0

3.0

15.7

5.7

20

35

20

70

70

30

M-C2E-C20

M-D8E-C20

M-F8E-C20

7269

20DB022

1

5.5

4.0

23.0

8.3

30

50

30

100

100

30

M-D8E-C25

M-F8E-C25

7269

20DB028

2

7.5

5.5

29.6

10.7

40

70

40

125

125

50

M-F8E-C32

7269

20DB042

3

11

7.5

44.5

16.0

60

100

60

175

175

70

M-F8E-C45

13630

20DB052

3

15

11

51.5

18.6

80

125

80

200

200

100

20DB070

4

18.5

15

72

25.9

90

175

90

300

300

100

20DB080

4

22

18.5

84.7

30.5

110

200

110

350

350

150

20DB104

5

30

113

40.7

150

250

150

475

350

150

22

84.7

30.5

125

200

125

350

300

150

20DB130

5

37

141

44.1

175

275

175

500

375

250

30

113

35.3

125

225

125

400

300

150

20DB154

6

45

167

60.1

225

350

225

500

500

250

37

141

50.9

200

300

200

500

450

250

20DB192

6

55

208

75.0

300

450

300

600

600

400

45

167

60.1

225

350

225

500

500

250

20DB260

6

66

255

96.7

300

575

300

750

750

400

55

199

71.7

225

450

225

600

600

400

(1)

Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.

(2)

Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(3)

Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.

(4)

Maximum allowable rating by US NEC. Exact size must be chosen for each installation.

(5)

Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.

(6)

Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.

(7)

Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.

(8)

The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See

Bulletin 140M Motor Protection Circuit Breakers Application Ratings

.

(9)

When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.