Essential requirements for ce compliance, Essential requirements for ce compliance -36 – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 50

Advertising
background image

1-36

Installation/Wiring

Essential Requirements for CE Compliance

Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet
the requirements of EN61800-3.

3. Standard PowerFlex 700S CE compatible Drive.

4. Review important precautions/attentions statements throughout this

document before installing drive.

5. Grounding as described on

page 1-4

.

6. Output power, control (I/O) and signal wiring must be braided, shield

cable with a coverage of 75% or better, metal conduit or equivalent
attenuation.

7. All shielded cables should terminate with proper shielded connector.

8. Conditions in

Table 1.U on page 36

Table 1.U PowerFlex 700S EN61800-3 EMC Compatibility

(1)

(1) External filters for First Environment installations and increasing motor cable lengths in Second Environment

installations are available. Roxburgh models KMFA (RF3 for UL installations) and MIF or Schaffner FN3258
and FN258 models are recommended. Refer to http://www.deltron-emcon.com and http://www.mtecorp.com
(USA) or http://www.schaffner.com, respectively.

Frame(s

)

Second Environment

First Environment Restricted Distribution

Restrict Motor Cable to 30 m (98 ft.)

Restrict Motor Cable to 150 m (492 ft.)

Any Drive and Option

Any Drive and Option

External Filter Required

1 - 6

Advertising