Parameter data in linear list format, Parameter data in linear list format -16 – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 70

Advertising
background image

3-16

Programming and Parameters

Parameter Data in Linear
List Format

No.

Name
Description

Values

Li

nka

b

le

Rea

d

-W

ri

te

Da

ta

T

yp

e

1

Motor NP Volts

Set to the motor nameplate rated volts.

Units:
Default:
Min/Max:

Volt
Calculated
75/705

✓ 16-bit

Integer

2

Motor NP FLA

Set to the motor nameplate rated full load amps. Range limited by three-second inverter
rating.

Units:
Default:
Min/Max:

Amps
Calculated
Calculated/Calculated

✓ Real

3

Motor NP Hertz

Set to the motor nameplate rated frequency.

Units:
Default:
Min/Max:

Hz
Calculated
2.0000/500.0000

✓ Real

4

Motor NP RPM

Set to the motor nameplate rated RPM.

Units:
Default:
Min/Max:

RPM
Calculated
1/30000

✓ 16-bit

Integer

5

Motor NP Power

Set to the motor nameplate rated power.

Units:
Default:
Min/Max:

Hp
Calculated
0.2500/3500.0000

✓ Real

6

Mtr NP Pwr Units

The power units shown on the motor nameplate.

Default:
Options:

0
0
1

Hp
Hp
W

7

Motor Poles

Set to the number of motor poles indicated on the motor nameplate. Only even numbers are
allowed.

Units:
Default:
Min/Max:

Pole
4
2/40

✓ 16-bit

Integer

8

Motor Inertia

Time, in seconds, for an uncoupled motor to accelerate from zero to base speed, at rated
motor torque. Calculated during autotune.

Units:
Default:
Min/Max:

Sec
0.400
0.0100/655.0000

✓ ✓ Real

9

Total Inertia

Time, in seconds, for a motor coupled to a load to accelerate from zero to base speed, at
rated motor torque. Calculated during autotune.

Units:
Default:
Min/Max:

Sec
2.0000
0.0100/655.0000

✓ ✓ Real

10

Speed Ref 1

Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
A value of 1.0 represents base speed of the motor.

Default:
Min/Max:

0.0000
-/+2200000000.0000

✓ ✓ Real

11

Spd Ref1 Divide

Par 10 [Speed Ref 1] is divided by this number. This number can be used to scale the value
of Par 10 [Speed Ref 1].

Default:
Min/Max:

1.0000
-/+2200000000.0000

✓ ✓ Real

12

Speed Ref 2

Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].
A value of 1.0 represents base speed of the motor.

Default:
Min/Max:

0.0000
-/+2200000000.0000

✓ ✓ Real

13

Spd Ref2 Multi

Par 12 [Speed Ref 2] is multiplied by this number. This number can be used to scale the
value of Par 12 [Speed Ref 2].

Default:
Min/Max:

1.0000
-/+2200000000.0000

✓ ✓ Real

14

Speed Ref 4

Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

15

Speed Ref 5

Sets the speed reference that the drive should use when selected by Par 16 [Speed Ref Sel].

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4[Motor NP RPM] = 1.0

✓ ✓ Real

16

Speed Ref Sel

Selects the source of the speed reference to the drive.

Default:
Options:

1
0
1
2
3

“Spd Ref DPI”
“Zero Speed”

4

“Spd Ref 4”

“Spd Ref 1

5

“Spd Ref 5”

“Spd Ref 2”

6

“Spd Ref DPI”

“Spd Ref 3

17

Jog Speed 1

Sets the speed reference that the drive should use when responding to bit 18 [Jog 1] of Par
152 [Applied LogicCmd].

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

18

Jog Speed 2

Sets the speed reference that the drive should use when responding to bit 23 [Jog 2] of Par
152 [Applied LogicCmd].

Units:
Default:
Min/Max:
Comm Scale:

RPM
0.0000
-/+14112.0000
Par 4 [Motor NP RPM] = 1.0

✓ ✓ Real

19

Atune Spd Ref

Sets the maximum speed of the motor during the Flux current and inertia tests.

Units:
Default:
Min/Max:
Comm Scale:

RPM
1499.4000
176.4000/1764.0000
Par 4 [Motor NP RPM] = 1.0

✓ Real