Motor cable lengths, Power terminal block, Cable entry plate removal – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 22: Power wiring access panel removal, Access panel removal

Advertising
background image

1-8

Installation/Wiring

Motor Cable Lengths

Typically, motor lead lengths less than 30 meters (100 feet) are acceptable.
Motor lead lengths of 30 meters (100 feet) to 246 meters (800 feet) require
shielded cable. If your application dictates longer lengths, refer to
publication 20D-TD001, Technical Data - PowerFlex 700S Drives, for
details.

Power Terminal Block

Figure 1.3

shows the typical location of the Power Terminal Block in Frame

1 drives. The terminal block is located in the bottom section of the drive on
Frame 2-5 drives.

Cable Entry Plate Removal

If additional wiring access is needed, the Cable Entry Plate on Frame 1-3
drives can be removed. Simply loosen the screws securing the plate to the
chassis. The slotted mounting holes assure easy removal.

Important: Removing the Cable Entry Plate limits the maximum

surrounding air temperature to 40

o

C (104

o

F).

Power Wiring Access Panel Removal

Access Panel Removal

Frame 3 drives utilize a panel/cover over the power wiring terminals. To
remove, simply slide it down and out.

Frame

Removal Procedure (Replace when wiring is complete)

1, 2 & 6

Part of front cover, see

page 1-2

.

3

Open front cover and gently tap/slide cover down and out.

4

Loosen the 4 screws and remove.

5

Remove front cover (see

page 1-2

), gently tap/slide panel up and out.

Advertising