Appendix c - application notes, Input voltage range/ tolerance, Appendix c – Rockwell Automation 20D PowerFlex 700S Drive Ph I Control, Frames 1...11 User Manual

Page 211: Application notes, Appendix

Advertising
background image

Appendix

C

Application Notes

For additional application notes, refer to the PowerFlex 700S Adjustable
Frequency AC Drive with Phase I Control - Reference Manual
, publication
PFLEX-RM002.

Input Voltage Range/
Tolerance

For Information on …

See Page...

Input Voltage Range/Tolerance

C-1

Motor Control Mode

C-2

Motor Overload

C-3

Overspeed Limit

C-4

Stop Dwell Time

C-5

Setpt 1 Data

C-6

Setpt 2 Data

C-6

Drive Rating

Nominal Line
Voltage

Nominal Motor
Voltage

Drive Full Power
Range

Drive Operating
Range

200-240

200

200†

200-264

180-264

208

208

208-264

240

230

230-264

380-400

380

380†

380-528

342-528

400

400

400-528

480

460

460-528

500-600
(Frames 1-4 Only)

600

575†

575-660

432-660

500-690
(Frames 5 & 6 Only)

600

575†

575-660

475-759

690

690

690-759

475-759

Drive Full Power Range =

Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated current is available across the entire Drive Full Power
Range

Drive Operating Range =

Lowest† Nominal Motor Voltage - 10% to Drive Rated Voltage +
10%.
Drive Output is linearly derated when Actual Line Voltage is less
than the Nominal Motor Voltage

HP

@ Motor (Drive Output)

Actual Line Voltage (Drive Input)

Full Power Range

Drive Operating Range

Nominal Motor Voltage -10%

Nominal Motor Voltage

Derated Power Range

No Drive

Output

Drive Rated Voltage

Drive Rated Voltage +10%