Setting the ip address selection jumper, Using default network address, Using dhcp server – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 18: Using option module parameters, Setting, The ip address selection

Advertising
background image

18

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Chapter 2 Installing the Option Module

Setting the IP Address

Selection Jumper

The IP Address Selection Jumper (

Figure 1

) determines the source of the

network address for the option module.

Figure 1 - Setting the IP Address Selection Jumper

Using Default Network Address

When the jumper is on Pins 2 and 3 and

Device Parameter 16 - [DHCP] is set to

‘0’ (Disabled), the following default network address is used:

• IP Address 192.168.0.1
• Subnet Mask 255.255.255.0
• Gateway 192.168.0.1

Using DHCP Server

When the jumper is on Pins 1 and 2 and

Device Parameter 16 - [DHCP] is set to

‘1’ (Enabled), the network address is configured from a DHCP server. To set an
IP address using a DHCP server, do the following.

1.

Set

Device Parameter 16 - [DHCP] to ‘1’ (Enabled) to select the DHCP

server as the source for the IP address.

2.

Reset the option module; see

Resetting the Option Module on page 33

, so

it can get the new IP address from the DHCP server.

Using Option Module Parameters

When the jumper is on Pins 1 and 2—or there is no jumper—and

Device

Parameter 16 - [DHCP]

is set to ‘0’ (Disabled), the network address is

configured with option module parameters.

1

3
2

Pin 2 and 3 (DEFAULT setting)
Pin 1 and 2 (CONFIG setting) to

use option module parameters or

DHCP server for network address