Option Module Parameters Appendix B

04
05
06
07

[IP Addr Cfg 1]
[IP Addr Cfg 2]
[IP Addr Cfg 3]
[IP Addr Cfg 4]
Sets the IP address bytes for the option module’s

network address when the IP Address Selection

Jumper (

Figure 1 on page 18

) is set on Pins 1 and

2—or the jumper is missing.

Important: To set the IP address using these

parameters, Device Parameter 16 - [DHCP] must

be set to ‘0’ (Disabled).

Default:

192

Default:

168

Default:

0

Default:

1

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required: Yes

08
09
10
11

[Subnet Cfg 1]
[Subnet Cfg 2]
[Subnet Cfg 3]
[Subnet Cfg 4]
Sets the subnet mask bytes for the option module’s

network address.

Important: To set the subnet mask using these

parameters, Device Parameter 16 - [DHCP] must

be set to ‘0’ (Disabled).

Default:

255

Default:

255

Default:

255

Default:

0

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required: Yes

12
13
14
15

[Gateway Cfg 1]
[Gateway Cfg 2]
[Gateway Cfg 3]
[Gateway Cfg 4]
Sets the gateway address bytes for the option

module’s network address.

Important: To set the gateway address using

these parameters, Device Parameter 16 - [DHCP]

must be set to ‘0’ (Disabled).

Default:

192

Default:

168

Default:

0

Default:

1

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details

255.255.255.255

[IP Addr Cfg 1]

[IP Addr Cfg 2]

[IP Addr Cfg 3]

[IP Addr Cfg 4]

255.255.255.255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

255.255.255.255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]