Restoring option – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Chapter 3 Configuring the Option Module

Restoring Option Module

Parameters to Factory

Defaults

As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using

Device Parameter 03 -

[Reset Module]

described in

Resetting the Option Module on page 33

. The

MEMORY folder method provides two ways to restore the option module

Device and Host parameters:

• ALL—restores ALL option module Device and Host parameters to their

factory default values.

• MOST—restores MOST option module Device and Host parameters—

except the following parameters which are used for network setup:

Device Parameters 04 through 07 - [IP Addr Cfg 1-4]

Device Parameters 08 through 11 - [Subnet Cfg 1-4]

Device Parameters 12 through 15 - [Gateway Cfg 1-4]

Device Parameter 16 - [DHCP]

Follow these steps to restore option module

Device and Host parameters to their

factory default values.

1.

Access the Status screen, which is displayed on HIM powerup.

2.

Use the

or

key to scroll to the Port in which the option

module is installed.

3.

Press the

key to display its last-viewed folder.

4.

Use the

or

key to scroll to the MEMORY folder.

5.

Use the

or

key to select Set Defaults.

6.

Press the

(Enter) key to display the Set Defaults pop-up box.

7.

Press the

(Enter) key again to display the warning pop-up box to

reset

Device and Host parameters to their factory default values.

8.

Press the MOST

soft key to restore MOST Device and Host parameters to

factory defaults, or press the ALL

soft key to restore ALL parameters. Or

press the ESC

soft key to cancel.

00

ESC

TEXT

Stopped

0.00 Hz

AUTO

Host Drive

240V

4.2A

Rev 3.002 Ser. A

F

REF

PAR#

Advertising