PORT Status Indicator

This red/green bicolor LED indicates the status of the option module’s
connection to the drive as shown in the table below.

MOD Status Indicator

This red/green bicolor LED indicates the status of the option module as shown
in the table below.

Status

Cause

Corrective Action

Off

The option module is not powered or is not

properly connected to the drive.

Securely connect and ground the option module to the

drive by fully inserting it into the drive port and

tightening its two captive screws to the recommended

torque.

Apply power to the drive.

Flashing Red

The option module is not receiving any

communication from the drive.

Verify that the option module is properly inserted in the

drive port.

Cycle power to the drive.

Steady Red

The option module detected a duplicate or invalid

port ID.

Important: Cycle power to the drive after securely

connecting and grounding the option module to the drive by

fully inserting it into the drive port and tightening its two

captive screws to the recommended torque.

Flashing Green

The option module is establishing communication

with the drive.

No action required. This status indicator will turn steady

green or red.

Steady Green

The option module is properly connected and

communicating with the drive.

No action required.

Steady Orange

The brand of the option module and drive do not

match.

Connect the option module to a compatible product of the

same brand (an Allen-Bradley PowerFlex 750-Series drive).

Status

Cause

Corrective Action

Off

The option module is not powered or is not

properly connected to the drive.

Securely connect and ground the option module to the

drive by fully inserting it into the drive port and

tightening its two captive screws to the recommended

torque.

Apply power to the drive and network.

Flashing Red

The option module has failed the firmware test.

Cycle power to the drive. Parameter settings may have

been changed.

Clear faults in the option module.
If cycling power does not correct the problem, the option

module parameter settings may have been corrupted.

Reset defaults and reconfigure the option module.

If resetting defaults does not correct the problem, update

the option module with the latest firmware revision.

Steady Red

The option module has failed the hardware test.

Cycle power to the drive.
Replace the option module.

Flashing Green

The option module is operating normally, but is

not transferring BACnet data.

Place the Client in RUN mode.
Configure the option module for the program in the

controller.

Program the controller to recognize and transmit BACnet

data to the option module.

Normal behavior if no communication is taking place.

Steady Green

The option module is operating and is

transferring BACnet data to the controller.

No action required.