Net a status indicator, Viewing option module diagnostic items – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 45

Advertising
background image

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

45

Troubleshooting Chapter 5

NET A Status Indicator

This red/green bicolor LED indicates the status of the network connection to the
option module as shown in the table below.

Viewing Option Module

Diagnostic Items

If you encounter unexpected communications problems, the option module’s
diagnostic items may help you or Rockwell Automation personnel troubleshoot
the problem. Option module diagnostic items can be viewed with any of these
drive configuration tools:

• PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 6.01 or later
• DriveExecutive software, version 5.01 or later

For details on viewing diagnostic items using the HIM, see the PowerFlex 20-
HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication

20HIM-UM001

.

Status

Cause

Corrective Actions

Off

The option module is not powered or is not

properly connected to the network. The link is

inactive.

Securely connect the option module to the drive and

connect it to the network with a CAT5 cable.

Correctly connect the network cable to the option

module’s RJ45 Ethernet connector.

Apply power to the drive.

Flashing Red

Any error in packet validation and/or execution is

considered a network configuration error.

Re-configure the option module.

Steady Red

Any failure in self-test on the external Ethernet

controller is considered a network controller

error.

Cycle power to the drive.
Re-configure the BACnet Client.

Steady Green

The option module is properly connected and

communicating on the network.

No action required.

Table 4 - Option Module Diagnostic Items

No.

Name

Description

1

Common Logic Cmd

The present value of the Common Logic Command being transmitted to the drive by this option module.

2

Prod Logic Cmd

The present value of the Product Logic Command being transmitted to the drive by this option module.

3

Reference

The present value of the Reference being transmitted to the drive by this option module.

4

Common Logic Sts

The present value of the Common Logic Status being received from the drive by this option module.

5

Prod Logic Sts

The present value of the Product Logic Status being received from the drive by this option module.

6

Feedback

The present value of the Feedback being received from the drive by this option module.

7

DPI Rx Errs

The present value of the DPI CAN Receive error counter register.

8

DPI Rx Errs Max

The maximum value of the DPI CAN Receive error counter register.

9

DPI Tx Errs

The present value of the DPI CAN Transmit error counter register.

10

DPI Tx Errs Max

The maximum value of the DPI CAN Transmit error counter register.

11

Boot Flash Count

The number of times the boot firmware in this option module has been updated.

12

App Flash Count

The number of times the application firmware in this option module has been updated.

Advertising