Set the subnet mask, Set the gateway address – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 27

Advertising
background image

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

27

Configuring the Option Module Chapter 3

2.

Set the value of

Device Parameters 04 - [IP Addr Cfg 1] through 07 - [IP

Addr Cfg 4]

to a unique IP address.

3.

Reset the option module; see

Resetting the Option Module on page 33

.

Set the Subnet Mask

1.

Verify that

Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).

2.

Set the value of

Device Parameters 08 - [Subnet Cfg 1] through 11 -

[Subnet Cfg 4]

to the desired value for the subnet mask.

3.

Reset the option module; see

Resetting the Option Module on page 33

.

Set the Gateway Address

1.

Verify that

Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).

2.

Set the value of

Device Parameters 12 - [Gateway Cfg 1] through 15 -

[Gateway Cfg 4]

to the IP address of the gateway device.

3.

Reset the option module; see

Resetting the Option Module on page 33

.

ESC

ENTER

Stopped

0.00 Hz

AUTO

Edit IP Addr Cfg 1

0

0 << 255

F

Default = 0.0.0.0

255.255.255.255

[IP Addr Cfg 1]

[IP Addr Cfg 2]

[IP Addr Cfg 3]

[IP Addr Cfg 4]

Stopped

0.00 Hz

F

Edit Subnet Cfg 1

0

0 << 255

ENTER

ESC

AUTO

Default = 0.0.0.0

255.255.255.255

[Subnet Cfg 1]

[Subnet Cfg 2]

[Subnet Cfg 3]

[Subnet Cfg 4]

ESC

ENTER

AUTO

F

Edit Gateway Cfg 1

0

0 << 255

Stopped

0.00 Hz

Default = 0.0.0.0

255.255.255.255

[Gateway Cfg 1]

[Gateway Cfg 2]

[Gateway Cfg 3]

[Gateway Cfg 4]

Advertising