Setting the Device Instance

A BACnet Device Instance number is used to identify a BACnet device over the
BACnet network. A Device Instance number must be unique across all subnets
and routed links.

The Device Instance number could be configured depending upon the adopted
network strategy. For example

Figure 3

shows a Building level network having

two individual floor networks through a router which allows devices on each
network to share the same IP address. Each device on the network in this example
has a unique Device Instance number consisting of 4 digits. The first digit
represents the Building or Floor number. The last 3 digits represent the fourth
octet of the device’s IP address.

Figure 3 - Building Automation Network Example

1.

Set the value of

Device Parameter 18 – [Device Instnc] to a unique

Device Instance number.

This Device Instance number should not be repeated within a BACnet
network. By default, the Device Instance number is set to 100.

2.

Reset the option module; see

Resetting the Option Module on page 33

so

that the new Device Instance number takes effect.

Building Level Network 1

Floor Level Network 1 (BACnet IP)

Building Level Network 2

Building

Controller 1

Other Brand

Building Automation

Product

IP Add. 192.168.120.121

Device Instance

1

001

IP Add. 192.168.120.122

Device Instance

1

002

IP Add. 192.168.120.123

Device Instance

1

050

IP Add. 192.168.120.124

Device Instance

1

127

Other Brand

Building Automation

Product

Router

Bldg 1/Flr 1

Building

Controller 2

Floor Level Network 1 (BACnet IP)

Other Brand

Building Automation

Product

IP Add. 192.168.112.211

Device Instance

2

001

IP Add. 192.168.112.212

Device Instance

2

002

IP Add. 192.168.112.213

Device Instance

2

050

IP Add. 192.168.112.214

Device Instance

2

127