Supported bacnet objects – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 40

Advertising
background image

40

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Chapter 4 Using BACnet Services and Objects

Supported BACnet Objects

The type of drive used on the network determines the specific BACnet objects
that are supported. See

Table 3

for descriptions of the BACnet objects and the

drives supporting those objects.

Table 3 - BACnet Object Descriptions and Supported Drives

Object

Name

Use this Object to...

Drive

Parameter

Number

PowerFlex 750-

Series Drive
753

755

Analog Input (AI) Objects

AI0

Analog Input 1 (%)

Read the value of Analog Input 1 (voltage or current) on the drive’s I/O

terminal block.

260

Analog Output (AO) Objects

AO0

Analog Output 1 (%)

Read/write the value of Analog Output on the drive’s I/O terminal block.

276

Analog Value (AV) Objects

AV0

Speed Reference A

Read/write the Speed Reference A.

AV1

Speed Reference B

Read/write the Speed Reference B.

AV2

Output Frequency (Hz)

Read the drive’s output frequency.

1

AV3

Output Current (Amps)

Read the drive’s output current.

7

AV4

Output Voltage (VAC)

Read the drive’s output voltage.

8

AV5

Output Power (kW)

Read the drive’s output power.

9

AV6

Output Energy (kWh)

Read/write the drive’s accumulated output energy.
Important: When writing, this object accepts only a value of ‘0’ (zero).

14

AV7

Output Energy 2 (MWh)

Read/write the drive’s accumulated Output energy in terms of MWh.
Important: When writing, this object accepts only a value of ‘0’ (zero).

13

AV8

DC Bus Voltage (VDC)

Read the drive’s DC bus voltage.

11

AV9

Drive Temp (°C)

Read the drive’s temperature.

944

AV10

Reserved

AV11

Run Time (Hours)

Read/write the drive’s accumulated run time.
Important: When writing, this object accepts only a value of ‘0’ (zero).

15

AV12

Fault 1

Read the code for the drive’s most recent fault.

DPI Fault

Object

AV13

Fault 2

Read the code for the drive’s second most recent fault.

DPI Fault

Object

AV14

Fault 3

Read the code for the drive’s third most recent fault.

DPI Fault

Object

AV15

Accel Time 1 (Sec)

Read/write the drive’s Accel Time 1 setting.

535

AV16

Accel Time 2 (Sec)

Read/write the drive’s Accel Time 2 setting.

536

AV17

Decel Time 1 (Sec)

Read/write the drive’s Decel Time 1 setting.

537

AV18

Decel Time 2 (Sec)

Read/write the drive’s Decel Time 2 setting.

538

AV19

Reference 1 (%)

Read/write the Reference 1.

545

AV20

Reference 2 (%)

Read/write the Reference 2.

550