Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 41

Advertising
background image

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

41

Using BACnet Services and Objects Chapter 4

AV21

Mailbox1 Param

Read/write any drive parameter.
To read a drive parameter, write the number for the desired parameter to

the Mailbox Param object, and then read the Mailbox value object.
To write a drive parameter, write the number for the desired parameter to

the Mailbox Param object, and then write the desired value to the

Mailbox Value object.

AV22

Mailbox1 Value

AV23

Mailbox2 Param

AV24

Mailbox2 Value

AV25

Mailbox3 Param

AV26

Mailbox3 Value

AV27

Mailbox4 Param

AV28

Mailbox4 Value

AV29

Mailbox5 Param

AV30

Mailbox5 Value

AV31

Mailbox6 Param

AV32

Mailbox6 Value

AV33

Mailbox7 Param

AV34

Mailbox7 Value

AV35

Mailbox8 Param

AV36

Mailbox8 Value

Binary Input (BI) Objects

BI0

Digital Input 0

Read the state of Digital Input 0 on the drive’s OBJECTS terminal block.

220 (Bit 0)

B11

Digital Input 1

Read the state of Digital Input 1 on the drive’s OBJECTS terminal block.

220 (Bit 1)

BI2

Digital Input 2

Read the state of Digital Input 2 on the drive’s OBJECTS terminal block.

220 (Bit 2)

Binary Output (BO) Objects

BO0

Output Relay 0

Read/write the state of Output Relay 0

227

Binary Value (BV) Objects

BV0

RUN Ready

Read the drive’s RUN Ready status.

Logic Status

Word, Bit 0

BV1

Active

Read the drive’s Active status, which is enabled if the drive is running.

Logic Status

Word, Bit 1

BV2

Forward/Reverse

Read the drive’s Actual Direction status, which is active if the drive is

running.

Logic Status

Word, Bit 3

BV3

Fault

Read the drive’s Fault status, which is active if the drive is faulted.

Logic Status,

Word, Bit 7

BV4

Alarm

Read the drive’s Alarm status, which is active if the drive has an alarm.

Logic Status

Word, Bit 6

BV5

At Setpt Spd

Read the drive’s Setpd Spd status, which is enabled if the drive is running

at the specified speed reference.

Logic Status

Word, Bit 8

BV6

Manual Active

Read the drive’s Manual Mode setting.
0 = Manual Mode Not Active; 1 = Manual Mode Active

Logic Status

Word, Bit 9

Table 3 - BACnet Object Descriptions and Supported Drives (Continued)

Object

Name

Use this Object to...

Drive

Parameter

Number

PowerFlex 750-

Series Drive
753

755