Setting the option module address using parameters, Disable the dhcp feature, Set the ip address – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 26: Using the powerflex 20-him-a6 or 20-him-c6s him to, Access parameters

Advertising
background image

26

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Chapter 3 Configuring the Option Module

Using the PowerFlex 20-

HIM-A6 or 20-HIM-C6S HIM

to Access Parameters

If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it
can be used to access parameters in the option module.

1.

Display the Status screen, which is shown on HIM powerup.

2.

Use the

or

key to scroll to the Port in which the option

module is installed.

3.

Press the PAR#

soft key to display the Jump to Param # entry pop-up box.

4.

Use the numeric keys to enter the desired parameter number, or use the

or

soft key to scroll to the desired parameter number.

For details on viewing and editing parameters, see the PowerFlex 20-HIM-A6/-
C6S HIM (Human Interface Module) User Manual, publication

20HIM-

UM001

.

Setting the Option Module

Address Using Parameters

By default, the option module is provided with the IP address 192.168.0.1,
subnet mask 255.255.255.0, and gateway address 192.168.0.1. If you want to set
these attributes using the option module parameters, you must first disable
DHCP and then set the associated option module parameters as described in the
following subsections.

Disable the DHCP Feature

1.

Set the value of

Device Parameter 16 - [DHCP] to ‘0’ (Disabled).

2.

Reset the option module; see

Resetting the Option Module on page 33

.

After disabling the DHCP feature, you can then configure the IP address, subnet
mask, and gateway address using option module parameters.

Set the IP Address

1.

Verify that

Device Parameter 16 - [DHCP] is set to ‘0’ (Disabled).

AUTO

ESC

ENTER

Stopped

0.00 Hz

F

Edit DHCP

Disabled

0

0 << 1

Value

Setting

0

Disabled

1

Enabled (Default)