Installing the Option Module Chapter 2

Table 1 - Drive and Option Module Start-Up Status Indications

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see

page 44

and

page 45

.

Item

Name

Color

Status

Description

Drive STS Indicator

STS

(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing

When running, a type 2 (non-configurable alarm condition exists – drive continues to run.

When stopped, a start inhibit condition exists and the drive cannot be started (see drive

parameter 933 - [Start Inhibits]).

Steady

A type 1 (user configurable) alarm condition exists, but the drive continues to run.

Red

Flashing

A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is

cleared.

Steady

A non-resettable fault has occurred.

Red/Yellow

Flashing Alternately

A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not

enabled, acts like a major fault. When running, the drive continues to run. System is

brought to a stop under system control. The fault must be cleared to continue.

Yellow/Green

Flashing Alternately

When running, a type 1 alarm exists.

Green/Red

Flashing Alternately

Drive firmware is updating.

Option Module Status Indicators

PORT

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module is not receiving any communication from the drive.

Steady

The option module detected a duplicate or invalid port ID.

Green

Flashing

Normal operation. The option module is establishing communication with drive. It will

turn steady green or red.

Steady

Normal operation. The option module is properly connected and communicating with the

drive.

Orange

Steady

The brand of the option module and drive do not match.

MOD

Off

The option module is not powered or connected properly to the drive.

Red

Flashing

The option module has failed the firmware test or a firmware update is in progress.

Steady

The option module has failed the hardware test.

Green

Flashing

Normal operation. The option module is operating but is not transferring I/O data to a

controller.

Steady

Normal operation. The option module is operating and transferring I/O data to a

controller.

NET A

Off

The option module is not powered or connected properly to the network. The link is

inactive.

Red

Flashing

Any error in packet validation and/or execution is considered a network configuration

error.

Steady

Any failure in self-test on the external Ethernet controller is considered a network

controller error.

Green

Steady

Normal operation. The option module is properly connected and communicating on the

network.

Advertising