Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Appendix B

Option Module Parameters

16

[DHCP]
Enables/disables the Dynamic Host Configuration

Protocol server for setting the IP address of the

option module.

Default:

0 = Disabled

Values:

0 = Disabled
1 = Enabled

Type:

Read/Write

Reset Required: Yes

17

[Comm Loss Time]
Sets the communication loss timeout period in

seconds. The value zero (0) disables this function.

Default:

10 seconds

Minimum:

0 seconds

Maximum:

180 seconds

Type:

Read/Write

Reset Required: No

18

[Device Instnc]
Sets the Device Instance number used by the

option module on the BACnet network.

Default:

100

Minimum:

0

Maximum:

65535

Type:

Read/Write

Reset Required: Yes

19

[Device Port]
Sets the network node Device Port for the option

module to enable BACnet messaging to be sent

and received over the BACnet/IP network.

Default:

47808

Minimum:

0

Maximum:

60000

Type:

Read/Write

Reset Required: Yes

20

[BBMD Port Number]
Sets the Port number for BACnet Broadcast

Management Device connection.

Default:

47808

Minimum:

0

Maximum:

60000

Type:

Read/Write

Reset Required: Yes

21
22
23
24

[BBMD Cfg 1]
[BBMD Cfg 2]
[BBMD Cfg 3]
[BBMD Cfg 4]
Sets the bytes in the IP Address of the BACnet

Broadcast Management Device.

Default:

0

Default:

0

Default:

0

Default:

0

Minimum:

0

Maximum:

255

Type:

Read/Write

Reset Required: Yes

Parameter
No. Name and Description

Details

ATTENTION: Risk of injury or equipment damage exists. Device

Parameter 17 - [Comm Loss Time] lets you determine how long it will

take the option module to detect a network communication loss. By

default, this parameter sets the timeout to ten (10) seconds. You can set

it so that the duration is shorter, longer, or disabled. When set to

disabled, this also disables Host Parameter 33 - [Comm Flt Action].

Therefore, a communication fault action will be ignored. Take

precautions to verify that the setting does not create a risk of injury or

equipment damage. When commissioning the drive, verify that your

system responds correctly to various situations (for example, a

disconnected cable).