Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014

Chapter 4 Using BACnet Services and Objects

BV10

Run/Stop

Read/write the drive’s Run/Stop command. Turn on this object to start the

drive/turn off bit to stop the drive.

Logic

Command

Word, Bit 18

BV11

Rev/Fwd

Read/write the drive’s Rev/Fwd command. Turn on this object to

command the reverse direction when the drive is running. Turn off this

object to command Forward.

Logic

Command

Word, Bits 4

and 5

BV12

Ref2/Ref1

Read/write the drive’s Ref2/Ref1 command. Turn on this object to select

the Reference 2 instance of the AV object as the drive’s speed reference.

Turn off this object to select Reference 1.

Logic

Command

Word, Bits

12, 13, and

14

BV13

Clear Faults

Read/write the drive’s Clear Faults command. Turn on this object to clear

the drive fault. Turning off this object does nothing.

Logic

Command

Word, Bit 3

BV14

Auto/Manual

Read/write the drive’s Auto/Manual setting.
0 = Not manual; 1 = Manual

Logic

Command

Word, Bit 6

Table 3 - BACnet Object Descriptions and Supported Drives (Continued)

Object

Name

Use this Object to...

Drive

Parameter

Number

PowerFlex 750-

Series Drive
753

755