160 SSC™ Variable Speed Controller (Series B)

3

Motor Cable

• The cable between the controller and motor must be a 4-wire

shielded cable (three phases and ground). Refer to Figures 2 & 3.

• When using a line filter module as specified in Appendix A, motor

cable lengths shall be limited to 75 meters (250 feet) for controllers
rated 200-240VAC and 40 meters (133 feet) for controllers rated
380-460VAC.

• Inside the shielded enclosure, shielded motor cable must be used

as close to the controller’s output terminals as possible. The shield
must be solidly connected to the PE terminal of the controller.

• Where the shielded motor cable exits the enclosure, an EMC-tested

cable clamp, or metal conduit must be used to solidly connect the
cable shield to the enclosure.

• The shield on the motor side must be solidly connected to the motor

housing with an EMC-tested cable clamp, or conduit, providing
good conductivity from the cable shield to the motor housing.

Figure 2 Motor Connections

Figure 3 Shielded Motor and Control Cable Example

Shielded Enclosure

U (T1)

V (T2)

W (T3)

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

* When the control circuitry is located outside of the 160 enclosure.

Motor Wiring TB2

L2

S

L1

R

L3

T

BR

BR

+

1 2 3 4 5 6 7 8 9 10 11

T2

V

TI
U

T3

W

DC

+

DC

Ground Tab – PE

FAULT

READY

4 Wire

Shielded Motor Cable

Ground to Motor Housing

Stranded Copper Wire

Plastic Insulation

Inner Plastic Sheath

Compact Screen of Galvanized (Tinned) Copper or Steel

Outer Plastic Jacket