Chapter 5 - Parameters and Programming

5–7

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

46

[Input Mode]

Configures the TB3 control inputs for either 3 wire" or 2 wire

run-fwd/run-rev control". Also enables/disables the program keypad module input
control. Note: This parameter cannot be programmed while the controller is
running. Also, power must be cycled for the change to take effect.

Settings:

0 = 3 wire" control
1 = 2 wire" control
2 = Program Keypad Module control
3 = Momentary ``Run Forward/ Run Reverse" Control

0 to 3

Numeric

Value

0

47

[Output Configure]

Configures the TB3 relay output functionality.

Settings

0 = Controller

Ready/Faulted

1 = At Frequency

2 = Controller Running

3 = Reverse

4 = Motor Overload
5 = Ramp Regulated

7= Above Current

6 = Above Frequency

Output changes state when...

8 = Above DC Bus

Voltage

energized and returns to shelf state when

power is removed or when a fault occurs.
the controller reaches commanded frequency.

the controller is running.

the controller is commanded to run in the reverse

direction.
when a motor overload condition exists.
the ramp regulator is modifying the

programmed accel/decel times to avoid an

overcurrent or overvoltage fault from occurring.
the controller exceeds the frequency value

set in P48 - [Output Threshold].
the controller exceeds the value set in P48 -

[Output Threshold]. Note: Value for P48 -

[Output Threshold] must be entered in % of

controller rated output current.
the controller exceeds the DC bus voltage value set

in P48 - [Output Threshold].

9 = Retries Exhausted

the number of retries for P50 - [Restart Tries] is

exceeded.

0 to 9

Numeric

Value

0

48

[Output Threshold]

Determines the on/off point for the TB3

output relay when [P47 - Output Configure] is set to 6, 7, and 8.

Settings

6

7

8

Ranges

0 to 240 Hz

0 to 150 %

0 to 815 Volts

0 to 815

Numeric

Value

0