Chapter 2 - Installation/Wiring

2–5

Control Wiring - Analog Signal Follower

Model

You can control the output frequency of the
controller via the Control Terminal Block (TB3)
using a remote potentiometer, a –10 to +10 VDC
analog input, a 4–20mA analog input, or P58 –
[Internal Frequency]
.

Note: Only one

frequency source may be connected at a time. If
the frequency reference potentiometer and the
4–20 mA reference are connected at the same
time, an undetermined frequency reference will
result. If the –10 to +10 VDC analog input is not
used, it should be tied to terminal block common
terminal 7 to improve noise immunity. Refer to
Chapter 5, parameters P58–P60 for factory
default settings.

À Control signal cable length is highly dependent on

electrical environment and installation practices. To

improve noise immunity the control terminal block

common must be connected to earth ground.

Consult factory for longer control signal cable length

applications.

Terminal

Max/Min

Wire Size

mm

2

(AWG)

Max/Min

Torque

Nm. (lb.in.)

2.5-0.5

(14-22)

0.8-0.4

(8-4)

TB3

Table 2.D Control Terminal Block Specifications

Control Wiring Requirements

D run all signal wiring in either a shielded

cable, or a separate steel conduit.

D only connect shield wire at control terminal

block common terminals 3 and 7

.

D do not exceed control wiring length of 15

meters (50 feet).

À

D use Belden 8760(or equivalent) – 18AWG

(0.750mm

2

), twisted pair, shielded or 3

conductor.

Control Wiring - Preset Speed Model

You can control the output frequency of the
controller via contact closure input to SW1,
SW2, and SW3. A program keypad module is
required to change the factory default settings.
Refer to Chapter 5, parameters 61–70 for the
eight preset frequency factory default settings
and switch configurations.

ATTENTION: The controller is
supplied with an internal 12V
supply. Dry contacts or open
collectors are required for discrete
control inputs. If an external
voltage is applied, component
failure could occur.

Note: Refer to the diagrams on the following
pages for control wiring information.

Wiring Diagrams