Chapter 2 - Installation/Wiring

2–4

Power Wiring For Preset Speed and

Analog Signal Follower Models

FAULT

READY

Terminal Block One (TB1) - For

Line Power and Brake Resistor.

S

T

-

L3

L2

L1

BR

BR

+

R

T

1

T

2

T3

+

V

DC

DC

-

U

W

Terminal Block Two (TB2) - For

Motor and Capacitor Module.

Required Branch

Circuit Disconnect

Â

Dynamic Brake Module

Option

Ã

Motor Å

Capacitor Module

Option

Ä

Ground Tab

 For single phase input applications, connect the AC input line

to input terminals (L1) R and (L2) S.

à Connection for dynamic brake resistors for all models. Note:

P52 - [DB Enable] must be enabled for proper operation.

See Appendix A for part numbers.

Ä Connection for an external capacitor module. Provides

extended ride through capability and improved inherent

braking performance. See Appendix A for part number.

Å Bulletin 160 controllers are and

listed as motor overload protective devices. An external

overload relay is not required for single motor applications.

Table 2.C Recommended AC Input Line Fuse

UL Class J, CC, or BS88 (or equivalent)

Input Line Fuses - See Table 2.C

above.

Â

Figure 2.3 - Power Wiring For Analog

Signal Follower and Preset Speed Models

Terminal Screw

Size

Max/Min

Wire Size

mm

2

(AWG)

Max/Min

Torque

Nm. (lb.in.)

M4

4-0.75

(12-18)

1.81-1.35

(16-12)

4-0.75

(12-18)

M4

TB1

TB2

Table 2.B

Power Terminal Block Specifications

ATTENTION:

Do not connect power factor

correction capacitors to controller output terminals

T1, T2, and T3 (U, V, and W)

.

1.81-1.35

(16-12)

ATTENTION:

The controller is

intended to be commanded by control input

signals that will start and stop the motor. A

device that routinely disconnects then

reapplies line power to the controller for the

purpose of starting and stopping the motor

should not be used. If it is necessary to use

this method for starting and stopping or if

frequent cycling of power is unavoidable,

make sure that it does not occur more than

once a minute.

3

Rating

kW (HP)

1

Rating

kW (HP)

Fuse

230V Rating

Fuse

460V Rating

( )

Denotes European sizes.

.37 (1/2)

-

6

3(4)

А

3(4)

А

15(16)

Б

10

Б

6

Б

6

10

15(16)

25

1.5 (2)

0.75 (1)

.55 (3/4)

.55 (3/4)

.37 (1/2)

.75 (1)

1.5 (2)
2.2 (3)

А Must be dual element time delay, Gould AJT or equivalent.

Á If blowing fuses is a problem, use dual element type fuses.