Chapter 5 - Parameters and Programming

5–9

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

54

[Clear Fault]

Setting this parameter to a 1" performs a fault reset. When

the fault reset function is complete, the value is automatically set back to 0".
Note: This parameter cannot be programmed while the controller is running.

0 to 1

Numeric

Value

0

55

[Memory Probe Address]

Used by Allen-Bradley field service

personnel.

Numeric Value

Numeric

Value

Numeric

Value

56

[Reset Defaults]

All parameters and their associated factory defaults are

reset when set to a value of 1". When the default function is complete, this
parameter will set itself back to a 0". This parameter cannot be programmed
while the controller is running. Note: An F48 - [Reprogram Fault] will occur
and must be cleared by cycling the STOP input to the controller.
Note: P46-[Input Mode Select] factory defaults to 3 wire" control. If using
keypad control, change parameter setting back to a 2" to regain program keypad
control.

0 to 1

Numeric

Value

0

57

[Program Lock]

When set to a 1", this parameter protects all controller

parameters from being changed by unauthorized personnel.

0 to 1

Numeric

Value

0

Program Group – Analog Signal Follower Model Only

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

ЙЙЙ

ЙЙЙ

ЙЙЙ

58

[Internal Frequency]

Digital frequency setpoint from the program

keypad module. Value of frequency command when P59 - [Frequency Select] is
set to a 1".

0 to 240

0.1 Hz

60.0

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

59

[Frequency Select]

Selects the source of the frequency command for

the controller.

Settings:

0 = frequency source from analog input to TB3 control terminal

block.
1 = frequency source from digital setpoint programmed into
P58 - [Internal Frequency].

0 to 1

Numeric

Value

0=Analog

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

ЙЙЙ

60

[Analog Scale Teach]

Scales the 0-10V

À

,4-20 mA analog input, or

remote potentiometer input to operate between P32 - [Minimum Frequency] and
P33 - [Maximum Frequency]. To scale to P33 - [Maximum Frequency], set
analog input to maximum value, increment parameter to a 1", and then press the
enter key. To scale to P32 - [Minimum Frequency], set analog input to minimum
value, increment parameter to a 2", and then press the enter key. Note: The
parameter resets to 0" after you press the enter key.

À

If you are using a bipolar input (-10 to +10V), do not scale the input to the

minimum frequency setting.

0 to 2

Numeric

Value

0

ЙЙЙ

ЙЙЙ

=

This parameter applies only to the Analog Signal Follower model.