Chapter 5 - Parameters and Programming

5–5

Program Groups

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

37

[Maximum Voltage]

Sets the highest voltage that the controller will

output.
P37 - [Maximum Voltage] must be greater than or equal to P36 - [Base Voltage].

20 to 460 for

460V units and

20 to 230 for

230V units

1 Volt

460 Volts for

460V units

and 230 for

230V units

38

[Boost Select]

Sets the boost voltage and redefines the Volts per Hz curve.

[Base Frequency], %

[Base V

oltage], % 50

100

1/2

Base

Volts

50

100

1/2

Base

Freq.

9

10

1

1

12

0

1

8

y

b

See Settings 1

through 8 below

Setting Boost Voltage % of [Base Voltage]

1

2.5

2

5.0

3

7.5

4

10.0

5

12.5

6

15.0

7

17.5

8

20.0

0

0

SettingFan/Pump Curves

А

А Break Point Voltages in %

of [Base Voltage].

9

45.0

10

40.0

11

35.0

12

30.0

0 to 12

Numeric

Value

4

39

[Skip Frequency]

Works in conjunction with P40 - [Skip Frequency

Band] creating a range of frequencies at which the controller will not operate
continuously.

'

b

y

Two times

P40-[Skip Freq Band

Setting

'

Skip

Frequency

Setting

Frequency

Time

Controller Output

Frequency

a

Command

Frequency

0 to 240

1 Hz

240 Hz

40

[Skip Frequency Band]

Determines the band around the P39 - [Skip

Frequency] parameter. The actual band width will be 2 times [Skip Frequency
Band] - 1/2 the band above and 1/2 the band below. A value of zero will disable
the skip frequency.

0 to 30

1 Hz

0 Hz