Chapter 5 - Parameters and Programming

5–6

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

41

[Motor Overload Select]

Selects the derating factor for the I

2

t

overload function.

Min Derating

Max Derating

% Base Speed

% Base Speed

0 25 50 75100 125 150 175 200

0 25 50 75 100125 150 175 200

[Overload Current]

%

of

Setting

[Overload Current]

%

of

Setting

100

80
60
40
20

100

80
60
40
20

Settings:

0 = No Derating
1 = Minimum Derating
2 = Maximum Derating

100

80
60
40
20

0 25 50 75 100 125150 175 200

% Base Speed

No Derating

[Overload Current]

%

of

Setting

0 to 2

Numeric

Value

0

42

[Motor Overload Current]

Set to motor nameplate full load Amps

(FLA).

25% to 200%

.01 Amperes

115% of

Controller

Rating

43

[Current Limit]

Maximum output current allowed before current limiting

occurs. Value set in percent of controller rated output current.

20% to 190%

1 %

150%

44

[DC Hold Time]

Time that P45 - [DC Hold Volts] voltage will be applied

to the motor when P34 - [Stop Mode Select] is set to either DC Brake" or
Ramp" mode.

0 to 15

1 Second

0 Seconds

45

[DC Hold Voltage]

DC Voltage level applied to the motor during braking

when P34 - [Stop Mode Select] is set to either DC Brake" or Ramp" mode.

0 to 115

1 Volt

0 Volts

[DC Hold Time]

y

Stop Command

[DC Hold Voltage]

Time

Speed

Voltage

Volts and Speed

DC Brake Mode

Volts and Speed

y

Voltage

Stop Command

[DC Hold Time]

[DC Hold Voltage]

Time

Speed

Ramp Mode