Chapter 5 - parameters and programming, Overview of parameters, Programming example – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual

Page 27: Parameters and programming

Advertising
background image

5

Chapter

Parameters and Programming

5–1

Overview of Parameters

This chapter covers both display and program parameters. Display parameters are read only (they
cannot be programmed), while program parameters can be changed to fit your motor control
requirements. You must have a Program Keypad Module to view/change display and program
parameters. The table below describes which parameters apply to the Preset Speed and Analog Signal
Follower models. Refer to the programming example below for programming instructions.

Parameter Type

Parameter Numbers

Analog Signal Follower Model

Preset Speed Model

Display

1 through 14

1 through 15

Program

30 through 60

30 through 57 and 61 through 70

The following pages contain descriptions of both display and program

parameters. Any parameter description that is shaded pertains only

to the Preset Speed or Analog Signal Follower model. Refer to the

legend to the right.

= Parameter applies only to the Preset Speed model

ÉÉ

= Parameter applies only to the Analog Signal Follower model

Programming Example

The following is an example of the programming steps required to change a program group parameter setting. In this example,

parameter 31 - [Decel Time] is changed from its factory default setting of 10.0 seconds to 2.2 seconds. Refer to Chapter 3, page

NO TAG for an explanation of Program Keypad Module display and programming keys. Note: To reset ALL values to original

factory default settings, refer to P56 - [Reset Defaults].

Action

Description

Keypad Display

1.

To program the value of a program group parameter, enter the program
group by pressing the ESCape key. The program mode indicator" will

illuminate.

2.

Press up/down keys until the desired parameter displays. In this case,
press the up key until parameter 31 - [Decel Time] displays.

3.

Press the SELect key. The program mode indicator flashes indicating
that you can use the up/down keys to change the parameter value.

4.

Change the decel time value from the factory default of 10 seconds to
2.2 seconds by pressing the down key until 2.2 displays.

Note:

Continuously holding the up or down key will cause the value to

increase or decrease as long as the key is pressed.

5.

When the desired value displays, press the ENTER key. This writes
the new value to memory. The program mode indicator will stop

flashing and the display will flash once indicating that the new value

has been accepted.

Note:

If at any time (while in the program mode) you wish to abort the

editing process, press the ESCape key. The original value of the parameter

will remain unchanged and you will be exited from the program mode.

3

0

0.

Program Mode Indicator

3

0

1.

3

0

Program Mode Indicator Flashes

1.

3

2

1.

2.

1

1

1

Program Mode Indicator

Stops Flashing

3 1.

2

0.

0.

0.

Program Mode Indicator

Stops Flashing

3

0

1.

1 0.

2.