Display group, 10 [controller type, 11 [control version – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual

Page 29: 12 [input status, 13 [power factor angle, 15 [preset status, Parameter description

Advertising
background image

Chapter 5 - Parameters and Programming

5–3

Display Group

P#

Parameter Description

Min/Max

Range

Units

10

[Controller Type]

Used by Allen-Bradley field service personnel.

Numeric Value

Numeric Value

11

[Control Version]

Displays version of controller firmware. Used by

Allen-Bradley field service personnel.

Fixed Value

Numeric Value

12

[Input Status]

Displays the open (0) and closed (1) state of the parallel

inputs in binary coded format.

Bit 3 Bit 2

Bit 1

Bit 0

Not Used

Stop

Reverse

Start

0000 to 0111

Binary Number

13

[Power Factor Angle]

Displays the angle in electrical degrees

between motor voltage and motor current.

0.00 to 90.00

0.01 degrees

БББ

БББ

БББ

14

[Memory Probe Display]

Used by Allen-Bradley field service

personnel.

БББББ

БББББ

БББББ

Numeric Value

БББББ

БББББ

БББББ

Numeric Value

15

[Preset Status]

Displays the open (0) and closed (1) state of Terminal

Block Three (TB3) inputs SW1, SW2, and SW3 in binary coded format. This
parameter applies to the Preset Speed model only.

Bit 3 Bit 2

Bit 1

Bit 0

Not Used

SW2

SW3

SW1

0000 to 0111

Binary Number

=

This parameter applies only to the Preset Speed model.

Advertising