Chapter 5 - Parameters and Programming

5–8

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

49

[PWM Frequency]

Carrier frequency for the PWM output waveform.

The chart below provides derating guidelines based on the PWM freq. setting.

1

2

3

4

5

6

7

8

84

86

88

90

92

94

96

98

100

%

Output

Current

(A)

Carrier Frequency, kHz

Note: Ignoring derating guidelines can cause reduced controller performance.

2.0 to 8.0

0.1kHz

4.0 kHz

50

[Restart Tries]

Maximum number of times the controller will attempt to

reset a fault.

0 to 9

Numeric

Value

0

51

[Restart Time]

Time between restart attempts.

0.5 to 300

0.1 Seconds

10.0

Seconds

52

[DB Enable]

Enables/disables dynamic braking. 0 = Disable, 1 = Enable

Note: This parameter cannot be programmed while the controller is running.

0 to 1

Numeric

Value

0

53

[S-Curve]

Enables a fixed shape S-Curve. See formula below:

1/2 SĆCurve

Time

a

'

a

'

a

'

a

'

a

'

a

'

1/2 SĆCurve

Time

À

See values in the Min/Max Range column

S-Curve Time = Accel or Decel Time x S-Curve" setting

(in percent)

À

S-Curve Time = 10 x .3

Example:

Accel Time = 10 seconds

S-Curve Setting = 3

= 3 Seconds

Enabled

Disabled

Accel Time

Decel Time

Note: Maximum
S-Curve time is 60
seconds.

Formula:

S-Curve

Setting

0 = 0%

1 = 10%

2 = 20%

3 = 30%

4 = 40%

5 = 50%

6 = 60%

7 = 70%

8 = 80%

9 = 90%

10 = 100%

Numeric

Value

0