Worldwide representation, 4160 ssc™ variable speed controller (series b), Figure 4 control connections – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual

Page 12: Control cabinet

Advertising
background image

160_5_9DU2.doc 4 Mon Sep 15 11:42:00 1997

4

160 SSC™ Variable Speed Controller (Series B)

Control Cable

• Control wiring must use shielded cable, or grounded metal conduit.

Refer Figures 3 and 4.

• The shield must be connected to signal common at both ends of

the cable.

• The Common terminals (TB3-3 & 7) must be solidly connected

(and as short as possible) to the PE terminal of the controller.

Figure 4 Control Connections

Shielded Enclosure

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

* When the control circuitry is located outside of the 160 enclosure.

Control Wiring TB3

L2

S

L1

R

L3

T

BR

BR

+

1

2

4

5

6

8

9 10 11

T2

V

TI

U

T3

W

DC

+

DC

Ground Tab – PE

FAULT

READY

Shielded Control

Cable

Signal
Common

Control

Cabinet *

to TB3

3

7

Rockwell Automation helps its customers receive a superior return on their investment by bringing
together leading brands in industrial automation, creating a broad spectrum of easy-to-integrate
products. These are supported by local technical resources available worldwide, a global network
of system solutions providers, and the advanced technology resources of Rockwell.

Worldwide representation.

Argentina • Australia • Austria • Bahrain • Belgium • Bolivia • Brazil • Bulgaria • Canada • Chile • China, People’s Republic of • Colombia • Costa Rica • Croatia • Cyprus
Czech Republic • Denmark • Dominican Republic • Ecuador • Egypt • El Salvador • Finland • France • Germany • Ghana • Greece • Guatemala • Honduras • Hong Kong
Hungary • Iceland • India • Indonesia • Iran • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Macau • Malaysia • Malta • Mexico
Morocco • The Netherlands • New Zealand • Nigeria • Norway • Oman • Pakistan • Panama • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia
Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic of • Spain • Sweden • Switzerland • Taiwan • Thailand • Trinidad • Tunisia • Turkey • United Arab Emirates
United Kingdom • United States • Uruguay • Venezuela

Rockwell Automation Headquarters, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414 382-2000, Fax: (1) 414 382-4444

Publication 160-5.9DU2 – May 1997

Copyright 1997 Rockwell International Corporation. All rights reserved. Printed in USA.

Advertising