Control wiring (continued) – Rockwell Automation 160 SER A FRN 1.XX-4.XX User Manual

Page 6

Advertising
background image

Document Update

DU–3

Control Wiring (continued)

Bulletin 160 Analog Signal Follower models (catalog # 160X–XAXXNSFlXX) can be operated using
either a unipolar (frequency control only) or bipolar (frequency and direction control) analog input. Use
Parameter 46 – [Input Mode] to select the control method for start, stop, and direction control.
There are
four settings from which to choose (shown in Table 2.E below). For all settings, the controller will reverse
when the voltage on the analog input transitions from positive to negative. In two-wire control (Parameter
46 – settings 1 and 3), negative voltage on the analog input will start the controller, which may be
unintended. This applies to both a negative offset in the analog command, or noise which causes the
analog input to go negative. Refer to Table 2.E below for the recommended installation instructions for
all Parameter 46 settings.

ATTENTION: Read the
following sections carefully before
installing the Bulletin 160 SSC.

Table 2.EąRecommended Wiring Instructions

Parameter 46

Direction Control

Analog Signal Follower Model

Preset Speed Model

Setting

UniĆpolar Input

BiĆpolar Input

Forward Only

0

Forward and

Reverse

Refer to Figure 2.6

Refer to Figure 2.6

Refer to Figure 2.6

Forward Only

Refer to Figure 2.7b

1

Forward and

Reverse

Refer to Figure 2.7c or 2.7d

Do not use this setting

Refer to Figure 2.7a

Forward Only

2

Forward and

Reverse

Refer to page 3Ć1

Refer to page 3Ć1

Refer to page 3Ć1

Forward Only

Consult factory for additional

3

Forward and

Reverse

Consult factory for additional

information prior to installation. Do not use this setting

Refer to Figure 2.8

ATTENTION: When changing the parameter setting for P46 – [Input Mode],
you must cycle power for the change to take effect.

ATTENTION: The program keypad module stop key simulates momentary pushbutton
operation. For “two wire” control schemes (P46 – [Input Mode], setting “1”) the
program keypad module stop button will only provide a “stop” function while the stop
key is depressed.