Chapter 4 - Start-Up

4–2

Reconnect the power to the

controller.

P01- [Output Frequency] will display. If the

controller has been previously powered up, a

different parameter number may display.

Note: To enable the start and reverse keys

from the program keypad module, set P46 -

[Input Mode] to a 2" and cycle power. Refer

to the programming example in Chapter 5.

If you have a program keypad module.

Do you have a Analog Signal

Follower controller or a Preset Speed

controller?

Analog Signal Follower controller

Preset Speed controller

Check for proper motor rotation by selecting P61 -

[Preset Frequency 0]. This requires removing all inputs

to SW1, SW2, and SW3 on TB3 [see Figure 2.5 in

Chapter 2]. The factory default setting for P61 - [Preset

Frequency 0] is 3 Hz.

If you have a blank display panel.

The READY [green] indicator

will illuminate. Use remote

inputs to TB3 control terminal

block to operate the controller.

Check for proper motor rotation by setting the frequency

source to its minimum setting.

If you are using a program keypad module, verify that the

CLOCKWISE LED is illuminated. If you are using a blank

display panel, verify that the REVERSE input to TB3 is in

the OPEN position.

Slowly increase the speed until the motor begins to turn.

Check the direction of the motor.

Is the direction of motor

rotation correct?

Yes

No

Startup is complete.

Disconnect and lock out all incoming power to TB1 terminals L1, L2, and L3 [R, S and T].

Issue a STOP command from either the program

keypad module or TB3 control block terminal.

If you are using a program keypad module, verify that the

CLOCKWISE LED is illuminated. If you are using a blank

display panel, verify that the REVERSE input to TB3 is in

the OPEN position.

Issue a START command from either the program keypad

module or TB3 control terminal block.

Issue a START command from either the program

keypad module or TB3 control terminal block. Check the

direction of motor rotation.

Issue a STOP command from either the program

keypad module or TB3 control block terminal.

ATTENTION:

A DC Bus voltage may be present at the

power terminal blocks (TB1) and (TB2) for approximately

one minute after power is removed from the controller.

Switch any two of the three motor leads connected to TB2, terminals T1, T2 and T3 [U, V and W].