Chapter 6 - Troubleshooting and Fault Information

6–2

Table 6.A Bulletin 160 Fault Descriptions

(continued)

Fault

Number

Fault

Indication

Fault Description

Corrective Action

ББББ

ББББ

ББББ

06

ББББ

ББББ

ББББ

Motor Stall

Fault

ББББББББББББ

ББББББББББББ

ББББББББББББ

Motor has stalled. Motor load is excessive.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Longer acceleration time or a reduced load required.

ББББ

ББББ

ББББ

07

ББББ

ББББ

ББББ

Motor

Overload

Fault

ББББББББББББ

ББББББББББББ

ББББББББББББ

Internal electronic overload trip. Excessive motor

load exists.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Reduce motor load until controller output current

does not exceed the current set by P42 - [Motor

Overload Current]. Reduce P38 - [Boost Volts].

ББББ

ББББ

ББББ

08

ББББ

ББББ

ББББ

Over

Temperature

Fault

ББББББББББББ

ББББББББББББ

ББББББББББББ

Excessive heat detected.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Clear blocked or dirty heat sink fins. Check ambient

temperature. Check for blocked or non-operating fan.

ББББ

ББББ

ББББ

12

ББББ

ББББ

ББББ

Overcurrent

FauIt

ББББББББББББ

ББББББББББББ

ББББББББББББ

Overcurrent detected in hardware trip circuit.

БББББББББББББ

БББББББББББББ

БББББББББББББ

Check short circuit at the controller output or excesĆ

sive load conditions at the motor.

22

Controller

Reset FauIt

Stop input not present.

Check stop connection at TB3, terminal 8.

32

EEPROM

Fault

EEPROM has invalid data.

Reset EEPROM using P56 - [Reset Defaults].

33

Max Retries

Fault

Controller failed to reset fault within the number

of retries set in P50 - [Restart Tries].

Repair system fault.

38

Phase U Fault Phase to ground fault detected between

controller and motor in phase U.

Check the wiring between the controller and motor.

Check motor for grounded phase.

39

Phase V Fault Phase to ground fault detected between

controller and motor in phase V.

Check the wiring between the controller and motor.

Check motor for grounded phase.

40

Phase W

Fault

Phase to ground fault detected between

controller and motor in phase W.

Check the wiring between the controller and motor.

Check motor for grounded phase.

41

UV Short

Fault

Excessive current has been detected between

these two controller output terminals.

Check the motor and external wiring to the controller

output terminals for a shorted condition.

42

UW Short

Fault

Excessive current has been detected between

these two controller output terminals.

Check the motor and external wiring to the controller

output terminals for a shorted condition.

43

VW Short

Fault

Excessive current has been detected between

these two controller output terminals.

Check the motor and external wiring to the controller

output terminals for a shorted condition.

46

Power Test

Fault

Fault detected during initial startĆup sequence.

Check controller wiring. Check motor wiring.

48

Reprogram

Fault

Occurs when controller parameters are reset to

defaults.

Clear fault.