B - specifications, Electrical, Environmental – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 113: Specifications, Appendix

Advertising
background image

Appendix

B

Specifications

Appendix B provides specification and supplemental information
for the 1336 REGEN Line Regeneration Package. Specifciations
apply to both the Regenerative DC Bus Supply and the
Regenerative Brake modes of operation unless noted.

Electrical

AC Main Supply and Auxiliary Voltage

380-480VAC, 3Ø, +10%/–15% Nominal
48-62Hz

90-115VAC, 1Ø, ±10% Nominal
48-62Hz

Environmental

Temperature
Ambient Operating Temperature

IP00 (Open) 0-50˚C
IP20 (NEMA Type 1) 0-40˚C

Storage Temperature

All Ratings -40 to +85˚C

Relative Humidity

5-95% Non-Condensing

Shock and Vibration
Shock

15g Peak for 11mSec. Duration (±1.0mSec.)

Vibration

0.152mm (0.0006 In.) Displacement, 1g Peak

ESD Susceptibility
IP20 (NEMA Type 1) Only

15kV

Agency Certification
U.L. Listed

CSA Certified

UL

®

LIST

ED 966X

IND CONT EQ

UL

®

LIST

ED 966X

IND CONT EQ

C

Advertising