4 - troubleshooting, Overview, Troubleshooting – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 93: Clearing a fault -1, Chapter

Advertising
background image

Chapter

4

Troubleshooting

Overview

Chapter 4 provides information to guide the user in
troubleshooting the 1336 REGEN Line Regeneration Package.
Included is a listing and description of the various faults that can
occur and their code numbers as they would appear on the HIM.
An additional section is included to document troubleshooting
from the 1336 REGEN Converter Control Board. (3) LEDs on the
Control Board provide status and fault information for the 1336
REGEN Line Regeneration Package.

Clearing a Fault

When a fault occurs, the Enable

&

Fault Output Relays will

change state and the 1336 REGEN Converter will shut down. Issu-
ing a reset command will clear the fault and reset the converter.
When a fault occurs however, the cause should be investigated and
action taken prior to resetting the fault.

Troubleshooting

1336 REGEN Converter Control Board LED Indication

LED

Status

Indicates

Off

No Faults Exist

On

A Fault Has Occurred — Refer to the Fault Codes Below

Off

No Power Has Been Applied to the Converter

On

The Converter Is Being Powered Up

On Flashing The Converter Has Tripped — Refer to the Fault Codes Below

Off

The Converter Is Not Enabled

On

The Converter Is Enabled

On Flashing The Converter Has Tripped — Refer to the Fault Codes Below

Off

The Converter Is Not Enabled

On
2 Flashes

A host checksum has occurred.

On
Continuous
Flashing

The Converter Has Tripped — Refer to the Fault Codes Below

DS1

FAULT

DS2

ENABLE

DS3

STATUS

DS4

COM