120vac precharge connections -19, 120vac connection specifications -19, 120vac precharge and converter wiring – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 71: B-d frames, Precharge

Advertising
background image

Regenerative Brake Operation

3–19

120VAC Precharge and
Converter Wiring

120VAC Precharge Connections

120VAC input and output connections are made to B-D Frame
Precharge Units as shown below.

Figure 3.11 — 120VAC Precharge Unit Connections

120VAC Connection Specifications

1. Use 75ºC Copper Wire Only.

2. Listed wires sizes are maximum/minimum wire sizes that the

terminals will accept — Not recommendations.

1336 REGEN PRECHARGE UNIT RATING

MAX/MIN WIRE SIZE

mm

2

(AWG)

MAX TORQUE
N-m (lb-in)

B-D Frames

2.1/0.30 (14/22)

0.90-1.13 (8-10)

1336 REGEN CONVERTER RATING

MAX/MIN WIRE SIZE

mm

2

(AWG)

MAX TORQUE
N-m (lb-in)

D Frame

2.1/0.30 (14/22)

0.90-1.13 (8-10)

CAT 1336R-PRE-VB180-AN

SER A

119-150

AC INPUT

K V A

VOLTS

A

PH

HZ

AC OUTPUT

DC OUTPUT

REFER TO USER MANUAL FOR
INSTALLATION INSTRUCTIONS

180.4

119-150

380-480

180.4 3

50/60

3

50/60

380-480

ALLEN-BRADLEY

AB MADE IN U.S.A.

UL

®

LIST

ED 966X

IN D

C O N T E

Q

UL

®

LIST

ED 966X

IN D

C O N T E

Q

C

®

!

DANGER

RISK OF SHOCK

REPLACE AFTER

SERVICING

R1

1

L1

3

L2

5

L3

S1

T1

TORQUE TERMINALS TO 275 LB-IN

USE 75˚C WIRE ONLY

1

3

TB1

1 = 120V

AC

3 = 120V

AC Common

B-D Frames

Precharge