Protection – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 114

Advertising
background image

B–2

Specifications

Protection

AC Input Overvoltage Trip

Factory Set to +15% of Nominal Line
Voltage

Heatsink Over Temperature Trip

100˚C

1336R Converter Overcurrent Trip

Software Overcurrent Limit

Factory Set to 192% of AC Input Current

Hardware Overcurrent Limit

Factory Set to 245% of AC Input Current

Line Transients

Up to 6000 Volts Peak per ANSI C62.41-1991

Control Logic Noise Immunity

Showering Arc Transients Up to 1500 Volts Peak

Power Ride-Thru

6 mSec. at Full Load

Control Logic Ride-Thru

0.5 Sec. Minimum, 2 Sec. Typical

Regenerative DC Bus Supply Mode
Only

380VAC Input

480VAC Input

Bus Overvoltage Trip

670VDC

850VDC

Bus Undervoltage Trip

430VDC

520VDC

Nominal Bus Voltage

610VDC

735VDC