Troubleshooting

4–3

Troubleshooting

Fault & Code No.

Status

Indicates

Action

Over Temperature

F 8

On

2 Flashes 5 Flashes Flashing

The 1336 REGEN Converter heat
sink temperature has exceeded
100˚C.

1. Check fan operation.

2. Check for blocked or dirty

cooling fins.

3. Confirm that the Converter’s

ambient temperature is within
the specifications listed in
Appendix B.

Bus Under Volts

F 9

On

2 Flashes 6 Flashes Flashing

Bus voltage has fallen below that
set by P17 - [BUV SW Trip].

Reset and re-enable the Converter.
Verify that the AC input line is within
the specifications listed in Appendix
B.

Contactor Out

F 10

On

3 Flashes 1 Flash

Flashing

The 1336 REGEN Precharge Unit’s
input contactor has opened.

Check the 115VAC contactor coil
supply.

External Fault

F 11

On

3 Flashes 2 Flashes Flashing

An external fault has been detected
at terminal 6 of J15 on the 1336
REGEN Converter Control Board.

Check that logic high is present at
terminal 6 of J15 on the 1336
REGEN Converter Control Board.

Line Over Volts1

F 12

On

4 Flashes 1 Flash

Flashing

The line-to-line voltage has
exceeded that set by P18 - [LOV
Trip 1]
.

1. Verify that the AC input line is

within the specifications listed in
Appendix B.

2. Reset and re-enable the

Converter.

Line Under Volt1

F 13

On

4 Flashes 2 Flashes Flashing

The line-to-line voltage has fallen
below that set by P20 - [LUV Trip
1]
.

1. Verify that the AC input line is

within the specifications listed in
Appendix B.

2. Reset and re-enable the

Converter.

Line Over Volt2

F 14

On

4 Flashes 3 Flashes Flashing

The line-to-line voltage has
exceeded that set by P19 - [LOV
Trip 2]
.

1. Verify that the AC input line is

within the specifications listed in
Appendix B.

2. Reset and re-enable the

Converter.

Line Under Volt2

F 15

On

4 Flashes 4 Flashes Flashing

The line-to-line voltage has fallen
below that set by P21 - [LUV Trip
2]
.

1. Verify that the AC input line is

within the specifications listed in
Appendix B.

2. Reset and re-enable the

Converter.

Open Fuse

F 16

On

5 Flashes 1 Flash

Flashing

1. 1336 REGEN Precharge Board

fuse F1, F2 or F3 has opened.
This fault will be detected only
on power up.

2. 1336 REGEN Converter line

fuse F1, F2 and F3 has opened.
This fault will be detected after
the converter is enabled.

1. Check fuse F1, F2 and F3 on

the Precharge Board if fault
occurs at power up.

2. Check bus fuse F1, F2 and F3 if

fault occurs after power up.