1336 regen fault and code number -2, Troubleshooting – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 94

Advertising
background image

4–2

Troubleshooting

Troubleshooting

1336 REGEN Fault and Code Number

Fault & Code No.

Status

Indicates

Action

Bus Over Volt HW

F 1

On

1 Flash

1 Flash

Flashing

Bus voltage has exceeded 130% of
the rated DC bus voltage —
— 537VDC for a 380VAC input.
— 650VDC for a 460VAC input.

1. Reduce the braking current limit

of the connected AC drive.

2. Reduce regeneration demand

on the connected AC drive by
reducing braking time.

3. Reset and re-enable the

Converter.

IOC HW

F 2

On

1 Flash

2 Flashes Flashing

Current has exceeded 198% of the
rated converter current.

1. Reduce the current limit of the

connected AC drive.

2. Check AC line fuses.

3. Reset and re-enable the

Converter.

4. If problem persists, replace the

Converter Control Board. If
problem reoccurs, check
Converter IGBT devices.

Bus Over Volt SW

F 4

On

2 Flashes 1 Flash

Flashing

Bus voltage has exceeded that set
by P16 - [BOV SW Trip].

1. Check the DC bus overvoltage

trip level set in P16.

2. Reduce regeneration demand

on the drive by reducing braking
time.

3. Ensure that the 1336 REGEN

Package is correctly sized for
the application.

IOC SW

F 5

On

2 Flashes 2 Flashes Flashing

1336 REGEN Converter input
current has exceeded that set by
P14 - [IOC SW Trip].

1. Check the instantaneous

overcurrent trip level set by P14.

2. Reduce the Converter’s current

limits.

3. Ensure that the 1336 REGEN

Package is correctly sized for
the application.

PLL Fault

F 6

On

2 Flashes 3 Flashes Flashing

A phase locked loop error has
exceeded the software trip point set
by P22 - [PLLReg Err Trip]. This
can occur for several reasons.

1. The utility voltage is corrupted or

unbalanced.

2. One of the line voltage feedback

inputs is missing.

1. Ensure that P22 - [PLLReg Err

Trip] is set correctly.

2. Verify that the utility’s voltage is

within the specifications listed in
Appendix B.

3. Check voltage feedback inputs

at the 1336 REGEN Precharge
Unit’s input contactor.

IT Fault

F 7

On

2 Flashes 4 Flashes Flashing

Current has exceeded 150% of
rated line current for (1) minute or
the equivalent IT value (current

×

time).

Reduce Converter loading.