Programming, Port enabled mask, Start/stop owner – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 50: Current command being issued, Logic status

Advertising
background image

2–34

Regenerative DC Bus Supply Operation

Programming

Parameter No.

23

Display Units

Bits

Parameter Type

Read/Write

Factory Default

111

Min/Max Value

0/7

Drive Units

N/A

Port Enabled Mask

This parameter sets the ability of a SCANport device to issue enable commands. The
commands are defined by the first (3) bits of a 16 bit word. The [Port Enable Mask] may be set
while the 1336 REGEN Converter is enabled.

Bit 0 = 1 When Bit 0 = 1, the system will be set to the auto-enable mode.

Bit 0 = 0 When Bit 0 = 0, this input requires an enable command from SCANport 1 or 2.

Parameter No.

24

Display Units

Bits

Parameter Type

Read Only

Factory Default

N/A

Min/Max Value

N/A

Drive Units

N/A

Start/Stop Owner

This parameter displays which adapter is currently issuing a valid enable command. Only the
first (3) bits of each byte are valid.

Parameter No.

25

Display Units

Bits

Parameter Type

Read Only

Factory Default

N/A

Min/Max Value

N/A

Drive Units

N/A

Current Command Being Issued

This parameter displays the logic command currently being issued.

Parameter No.

26

Display Units

Bits

Parameter Type

Read Only

Factory Default

N/A

Min/Max Value

N/A

Drive Units

N/A

Logic Status

This parameter displays the current logic status of the 1336 REGEN Converter.

n a b l e M a s k

E

o r t

P

1 1

2 3

1

X X X X

X

Bit 2

Bit 1

Bit 0

0 = Autoenable Not Allowed

1 = Autoenable Allowed

0 = SCANport 1 Enable Not Allowed

1 = SCANport 1 Enable Allowed

0 = SCANport 2 Enable Not Allowed

1 = SCANport 2 Enable Allowed

t o p O w n e r

S

t a r t

S

0

0

0

1

2 4

0

0

0

0

0

0

0

0

0

0

0

0

Bit 2

Bit 1

Bit 0

0 = Digital Input Enable Present

1 = Digital Input Enable Not

Present
0 = SCANport 1 Stop Not Present

1 = SCANport 1 Stop Present

Bit 10

Bit 9

Bit 8

0 = Digital Input Enable Not Present

1 = Digital Input Enable

Present
0 = SCANport 1 Start Not Present

1 = SCANport 1 Start Present

d S t a t u s

n

o m m a

C

0 1

2 5

0

0 0 0 0

0

Bit3

Bit 1

Bit 0

0 = Stop Command Inactive

1 = Stop Command Active

0 = Enable Command Inactive

1 = Enable Command Active

0 = Clear Fault Command Inactive

1 = Clear Fault Command

0 = Reset Command Not Present

1 = Reset Command Presen

Bit15

S t a t u s

o g i c

L

0 0

2 6

0

0 0 0 0

0

Bit 1

Bit 0

0 = Converter Not Ready

1 = Converter Ready

0 = Converter Not Enabled

1 = Converter Enabled

0 = Converter Not Faulted

1 = Converter Faulted

Bit 7