Heat dissipation, Altitude derating, Communications format and configuration – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 115

Advertising
background image

Specifications

B–3

Heat Dissipation

Altitude Derating

Communications Format
and Configuration

Logic Status Structure

This provides the drive status information that will be sent to the
logic controllers input image table when the communication
module is set to control converter.

Regenerative DC Bus Supply Operation Only — 380-480VAC Input

1336 REGEN
Package
Amp Rating

Converter

Converter
Heatsink

Precharge
Unit

10%
Line
Reactor

Power
Line
Filter

Package
Total

48A

141W

820W

15W

186W

173W

1335W

78A

193W

1110W

29W

258W

236W

1826W

180A

522W

2664W

58W

474W

317W

4035W

Regenerative Brake Operation Only — 380-480VAC Input

1336 REGEN
Package
Amp Rating

Converter

Converter
Heatsink

Precharge
Unit

3%
Line
Reactor

Package
Total

48A

141W

656W

15W

65W

877W

78A

193W

888W

29W

84W

1194W

180A

522W

2131W

58W

168W

2879W

m

(ft)

% of Rated Amps

100%

80%

90%

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

Altitude

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Bit 15

Bit 14

Bit 13

Bit 12

Bit 11

Bit 10

Bit 9

Bit 8

Ready

Enabled

Not Used

Faulted

Not Used