Input fusing, Customer supplied fusing -4, 1336 regen precharge fusing -4 – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 20

Advertising
background image

2–4

Regenerative DC Bus Supply Operation

Input Fusing

Customer Supplied Fusing

Based on the maximum 1336 REGEN Package voltage rating, the
following customer supplied fuses are recommended.

1336 REGEN Precharge Fusing

The 1336 REGEN Precharge Circuit Board is internally fused to
protect precharge components. When replacing 1336 REGEN
Precharge Unit fuses F1, F2

&

F3 (shown in Figure 2.12), use only

the type and size specified below.

!

ATTENTION: 1336 REGEN equipment does not
provide input power short circuit fusing. Branch circuit
breakers or disconnect switches cannot provide this
level of protection for converter and precharge unit
components. Specifications for the recommended fuse
size and type to provide input power protection against
short circuits at the Converter or Precharge Unit is listed
below.

!

ATTENTION: To guard against personal injury and/or
equipment damage caused by improper fusing, use only
the recommended line fuses specified.

Gould Shamut
A70QS must be
used for all 1336
REGEN Line
Regeneration
Packages.

Catalog Number

380-480VAC Rating

Input AC Line Fusing Output DC Bus Fusing

1336R-VB048

70A

100A

1336R-VB078

125A

150A

1336R-VB180

250A

350A

Catalog Number

380-480VAC Rating

1336R-VB048PRE

FNQ-R4, 600V

1336R-VB078PRE

FNQ-R4, 600V

1336R-VB180PRE

FNQ-R8, 600V