Programming – Rockwell Automation 1336R REGEN LINE REG User Manual

Page 88

Advertising
background image

3–36

Regenerative Brake Operation

Programming

Parameter No.

11

Display Units

Number

Parameter Type

Read/Write

Factory Default

5

Min/Max Value

1/10

Drive Units

1 = 4096

Instantaneous Overcurrent Trip Filter Constant

This parameter adjusts a software filter to prevent nuisance tripping due to severe, repeated
and prolonged line notches and voltage sags on the utility system. The default factory setting of

5

should be adequate for the majority of line and load conditions.

Example:

For a setting of

5:

The converter will fault if line current reaches the HW Overcurrent Trip Point
after approximately (5) consecutive sampling intervals.

If (3) consecutive hardware trip conditions occur, the converter will not fault.

If fault conditions disappear after (3) counts, the filter will discharge towards
zero at a rate (10) times less that the one it was initially charged up at.

If fault conditions reappear before the filter discharges to zero, it will start
counting up again from the internal value it reached during discharge towards
zero and quickly reach the HW Overcurrent Trip point.

Parameter No.

13

Display Units

%

Parameter Type

Read/Write

Factory Default

-150%

Min/Max Value

-150/0

Drive Units

100 = 4096

Regen Current Limit

Sets the actual negative or regenerating AC line current limit in percent of P-2 [Rated AC Line
Current]
.

Important: The 1336 REGEN Converter cannot be enabled for the [Regen Curr Limit] to be

changed.

Parameter No.

14

Display Units

%

Parameter Type

Read/Write

Factory Default

192% I

RATE

Min/Max Value

100/200% I

RATE

Drive Units

100 = 4096

Instantaneous Overcurrent Trip Level

This parameter sets the software trip point for the

Instantaneous SW Overcurrent Fault

in

percent of P-2 [Rated AC Line Current].

I

RATE

Amps = the rated nameplate current of the 1336 REGEN Converter [Rated AC Line

Current].

Important: The 1336 REGEN Converter cannot be enabled for the [IOC SW Trip] to be

changed.

Parameter No.

15

Display Units

Hz

Parameter Type

Read/Write

Factory Default

9.8

Min/Max Value

0.5/100

Drive Units

1.0 = 4096

Voltage Feedback Filter Bandwidth

This parameter sets the bandwidth of a first order filter used for AC line voltage feedback.
Increasing the bandwidth can help avoid nuisance trips due to short term AC line overvoltage
or undervoltage conditions.

Important: The 1336 REGEN Converter cannot be enabled for the [Volt Trp Fltr BW] to be

changed.